Basic Operation

6.3.2 V/f Pattern Selection: E1-03

6 - 24

J

Setting a User-defined V/f Pattern: E1-03 = “F”

D

Constants E1-04 through E1-10 can be set by the user when E1-03 has been set to “F.” These constants

are read-only when E1-03 isn’t set to “F.”

D

When making the V/f characteristics a straight line, set the same value in E1-07 (middle output frequen-

cy) and E1-09 (minimum output frequency). In this case, constant E1-08 (middle output frequency volt-

age) will be disregarded.

D

The user constant numbers for motor 2 are given in parentheses.

Settings for E1-04 to E1-10 (E4-01 to E4-07) and E1-13

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-04

(E4-01)

Max. output frequen-

cy
(FMAX)

x

50.0 to

150.0

Hz

60.0

Q

Q

Q

Q

E1-05

(E4-02)

Max. voltage
(VMAX)

x

0.0 to 510.0

*1

VAC 400.0

*1

Q

Q

Q

Q

E1-06

(E4-03)

Base frequency
(FA)

x

0.0 to 150.0

Hz

60.0

Q

Q

Q

Q

E1-07

(E4-04)

Mid. output frequen-

cy
(FB)

x

0.0 to 150.0

Hz

3.0

*2

Q

Q

A

X

E1-08

(E4-05)

Mid. output frequen-

cy voltage
(VC)

x

0.0 to 510.0

*1

VAC

24.0

*1,

*

2

Q

Q

A

X

E1-09

(E4-06)

Min. output frequen-

cy
(FMIN)

x

0.0 to 150.0

Hz

1.5

*2

Q

Q

Q

A

E1-10

(E4-07)

Min. output frequen-

cy voltage
(VMIN)

x

0.0 to 510.0

*1

VAC

12.0

*1, *2

Q

Q

A

X

E1-13

Base voltage
(VBASE)

x

0.0 to 510.0 VAC

0.0

*3

A

A

Q

Q

* 1. These values are for 400-VClass Inverters; multiply the values by approx. 1.5 for 575-VClass

Inverters.

* 2. The factory setting depends on the Inverter capacity. The factory settings shown in the table

are for 400-V Class, 200 to 800 kW Inverters. (See page 8 - 41.)

Refer to the graphs for “Setting: 1” on page 6 - 23.

* 3. If E1-13 is set to 0.0, E1-13 will be set to the same value as E1-05 following autotuning and

does not need to be set.

D

The factory settings for E1-07 through E1-10 will be set according to the control method whenever the

control method is changed. The factory settings shown in the table are for V/f control. See page 8 - 41.)

D

The four frequency settings must satisfy the following formula:

E1-04 (F

MAX

) ≥ E1-06 (F

A

) > E1-07 (F

B

) ≥ E1-09 (F

MIN

)

6