7.5 Common Functions

7 - 85

Setting

Function

0

Disabled.

1

Enabled.

D

This setting enables or disables the motor overload protection function.

D

The rated current setting (E2-01) is used as a basis for overload detection.

D

Disable the motor protection function (setting 0) when two or more motors are connected to a single

Inverter. Use another method to provide overload protection separately to each motor, such as connect-

ing a thermal overload relay to the power line of each motor.

D

The motor protection function may not protect a motor when the power supply is turned ON and OFF

frequently, because the thermal value is reset each time that the power is turned OFF.

D

If the Overload OL1 alarm (1F) is set in one of the multi-function outputs (H2-01 to H2-03), the output

will be turned ON when the electronic thermal value reaches 90% of the overload detection level.

Motor Protection Time Constant: L1-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L1-02

Motor protection time

constant

x

0.1 to 5.0

Min-

utes

1.0

B

B

B

B

D

Normally it isn’t necessary to change this setting. (The factory setting is a 150%, 1 minute capacity.)

D

Set the electronic thermal protection operation time if a 150% overload is applied after operating contin-

uously at the motor’s rated current (hot start).

D

When the motor’s overload capacity level is known, set the hot-start overload resistance level for the

motor, but be sure to allow some margin for safety.

D

Decrease this setting when you want to detect an overload more quickly.

Operating time (minutes)

10

7

3

1

0.4

0.1

0

100

150

200

Cold start

Hot start

Motor current (%)

(E2-01 is 100%.)

Electronic Thermal Time Characteristics

In this example, L1-02 is set to 1 minute, the motor is operating at 60 Hz, and general-purpose

motor characteristics are used.

Fig 7.42

Motor Protection Operating Time

J

Momentary Power Loss Settings: L2-01 to L2-06

Momentary Power Loss Detection: L2-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L2-01

Momentary power

loss detection

x

0 to 2

--

0

B

B

B

B

D

Settings