7.5 Common Functions

7 - 71

Detection method:

Always or During operation only

Operation selection:

Deceleration to stop, Coast to stop, Emergency stop, or Continue operation

Table 7.9 External Fault Settings

Input level

Detection method

Operation selection

Setting

NO con-

tact

NC con-

tact

Always

During

operation

Decelera-

tion to

stop

(Fault)

Coast to

stop (Fault)

Emergen-

cy stop

(Fault)

Continue

operation

(Alarm)

20

f

f

f

21

f

f

f

22

f

f

f

23

f

f

f

24

f

f

f

25

f

f

f

26

f

f

f

27

f

f

f

28

f

f

f

29

f

f

f

2A

f

f

f

2B

f

f

f

2C

f

f

f

2D

f

f

f

2E

f

f

f

2F

f

f

f

D

For the input level, select whether you want a fault to be detected when the input signal is ON (normally

open input) or OFF (normally closed input).

D

For the detection method, select whether you want faults to be detected any time that the Inverter is ON

or only during operation.

D

For the operation selection, select the processing method that you want to be performed when a fault

has been detected.

Deceleration to stop: A fault is output and the output stopped in the selected deceleration time.

Coast to stop: A fault is output and the Inverter output is cut off.

Emergency stop: A fault is output and the output stopped in the emergency stop time (C1-09).

Continue operation: An alarm is output and operation continues.

D

When an alarm is going to be output externally, be sure to set one of the multi-function outputs (H2-01,

02, and 03) to alarm (setting 10).

D

An external fault setting cannot be set in more than one multi-function input.

D

Unlike other constant settings, the external fault settings have an input procedure, as shown in the fol-

lowing diagrams.

Setting Procedure

1. When setting an external fault function, press the Enter Key when “External Fault” is displayed to bring