Motor 2 setup: e5 – Yaskawa G5HHP Drive User Manual

Page 288

Advertising
background image

User Constants

8.2.4 Motor Constant Constants: E

8 - 22

J

Motor 2 Setup: E5

C

t t

Name

S tti

F t

Change

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

Change

during

Opera-

tion

V/f

V/f

with

PG

Open

Loop

Vector

Flux

Vector

Page

E5-01

Motor 2 rated current

Sets the motor rated current in 1 A

units.
;

These set values will become the

reference values for motor

protection torque limits and

37.0 to

740.0

370.0

x

A

x

A

x

7 8

E5-01

Motor 2 rated FLA

protection, torque limits and

torque control.

These values will automatically

be set if they were set during au-

totuning.

740.0

*2

370.0

*1

x

A

x

A

x

7 - 8

E5-02

Motor 2 rated slip

Sets the motor rated slip in Hz

units.
;

These set values will become the

f

l

f

li

0.00 to

1.30

x

A

x

A

x

7 8

E5-02

Motor 2 Slip Freq

;

reference values for slip com-

pensation.

These values will be automati-

cally set during autotuning.

0.00 to

20.00

1.30

*1

x

A

x

A

x

7 - 8

E5-03

Motor 2 no-load cur-

rent

Sets the motor no-load current in 1

A units.
;

Th

l

ill b

t

ti l

0.00 to

2000 0

96.0

*1

x

A

x

A

x

7 - 8

E5 03

Motor 2 No-load 1

;

These values will be automatical-

ly set during autotuning.

2000.0

*1

x

A

x

A

x

7 - 8

E5-04

Motor 2 number of

poles

Sets the number of motor poles.
;

These values will automatically

2 to 48

4

x

x

x

x

x

---

E5 04

Motor 2 # Poles

;

These values will automatically

be set during autotuning.

2 to 48

4

x

x

x

x

x

---

E5-05

Motor 2 line-to-line

resistance

Sets the motor phase-to-phase re-

sistance in Ω units.
;

Th

l

ill b

t

ti l

0.000 to

65 000

0.020

*1

x

A

x

A

x

7 - 8

E5 05

Motor 2 term Ohms

;

These values will be automatical-

ly set during autotuning.

65.000

*1

x

A

x

A

x

7 - 8

E5-06

Motor 2 leak induc-

tance

Sets the voltage drop due to motor

leakage inductance as a percentage

of the motor rated voltage.

0.0 to

30 0

5.0

*1

x

x

x

A

x

7 - 9

E5 06

Motor 2 Leak

g

;

These values will be automatical-

ly set during autotuning.

30.0

*1

x

x

x

A

x

7 - 9

* 1. The factory setting depends upon the Inverter capacity. The values for a 400-V class Inverter of 200 kW will be displayed. See

page 8 - 42.

* 2. The setting range is 10% to 200% of the Inverter’s rated output current. The values for a 400-V class Inverter of 200 kW will

be displayed.