Multi-function output settings: h2 – Yaskawa G5HHP Drive User Manual

Page 240

Advertising
background image

Advanced Operation

7.5.5 External Terminal Functions: H

7 - 76

J

Multi-function Output Settings: H2

The settings and functions for the multi-function outputs are listed in Table 7.10.

Table 7.10 Multi-function Output Functions

Control Methods

Setting

value

Function

V/f

V/f

w/

PG

Open

loop

Vec-

tor

Flux
vec-

tor

0

During run ON: run command is ON or voltage is being output)

f

f

f

f

1

Zero-speed

f

f

f

f

2

Frequency agree 1: (Detection width L4-02)

f

f

f

f

3

Desired frequency agree 1 (ON: Output frequency = ±L4-01, detection width in L4-02)

f

f

f

f

4

Frequency (Four) detection 1 (ON: +L4-01≧output frequency≧--L4-01, detection width in L4-02)

f

f

f

f

5

Frequency (Four) detection 2
(ON: Output frequency≧+L4-01 or output frequency≦--L4-01, detection width in L4-02)

f

f

f

f

6

Inverter operation ready

READY: After initialization, no faults

f

f

f

f

7

During DC bus undervoltage (UV) detection

f

f

f

f

8

During baseblock (ON: during baseblock)

f

f

f

f

9

Frequency reference selection (ON: Frequency reference from Operator)

f

f

f

f

A

Run command selection (ON: Run command from Operator)

f

f

f

f

B

Overtorque detection 1 NO (NO contact: Overtorque detection at ON)

f

f

f

f

C

Loss of frequency reference (Effective when operation selection is “1” for L4-05 frequency reference missing)

f

f

f

f

D

Braking resistor fault (ON: Resistor overheat or braking transistor fault)

f

f

f

f

E

Fault (ON: Faults other than CPF00, CPF01 have occurred.)

f

f

f

f

F

Not used. (Do not set.)

--

--

--

--

10

Minor fault (ON: Alarm displayed)

f

f

f

f

11

Fault reset command active

f

f

f

f

12

Timer function output

f

f

f

f

13

Frequency agree 2 (Detection width: L4-04)

f

f

f

f

14

Desired frequency agree 2 (ON: Output frequency = L4-03, detection width in L4-04)

f

f

f

f

15

Frequency detection 3 (ON: Output frequency ≦--L4-03, detection width in L4-04)

f

f

f

f

16

Frequency detection 4 (ON: Output frequency ≧--L4-03, detection width in L4-04)

f

f

f

f

17

Overtorque detection 1 NC (NC Contact: Ttorque detection at OFF)

f

f

f

f

18

Overtorque detection 2 NO (NO Contact: Torque detection at ON)

f

f

f

f

19

Overtorque detection 2 NC (NC Contact: Torque detection at OFF)

f

f

f

f

1A

During reverse run (ON: During reverse run)

f

f

f

f

1B

During baseblock 2 (OFF: During baseblock)

f

f

f

f

1C

Motor selection (Motor under selection)

--

--

--

--

1D

Regenerating (ON: Regenerating)

f

1E

Restart enabled (ON: Restart enabled)

f

f

f

f

1F

Motor overload (OL1) pre-alarm (ON: 90% or more of the detection level)

f

f

f

f

20

Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting)

f

f

f

f

30

During torque limit (current limit) (ON: During torque limit)

x

x

f

f

31

During speed limit. (ON: During speed limit)

x

x

x

f

33

Zero-servo end (ON: Zero-servo function completed)

x

x

x

f

37

During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, initial excitation, operation stop.

f

f

f

f

7

Advertising