3 setting motor constants, Hunting prevention selection: c7-01, Hunting prevention gain: c7-02 – Yaskawa G5HHP Drive User Manual

Page 177: Motor rated slip: e2-02, Motor no-load current: e2-03

Advertising
background image

7.2 Normal V/f Control

7 - 13

J

Hunting Prevention Selection: C7-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C7-01

Hunting prevention

selection

x

0, 1

--

1

A

A

x

x

D

Settings

Setting

Function

0

Disables the hunting-prevention function.

1

Enables the hunting-prevention function.

J

Hunting Prevention Gain: C7-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C7-02

Hunting prevention

gain

x

0.00 to 2.50 Mul-

tiple

1.00

A

A

x

x

Normally it isn’t necessary to change these constants. Adjust these constants as follows if hunting occurs

with a light load.

D

Increase the setting in C7-02 if oscillation occurs when operating with a light load.

(If the setting is increased too much, the current can fall to the point where stalling occurs.)

D

Decrease the setting in C7-02 if stalling occurs.

D

Disable the hunting-prevention function (C7-01 = 0) if high responsiveness is more important than sup-

pressing oscillation.

7.2.3 Setting Motor Constants

J

Motor Rated Slip: E2-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E2-02

Motor rated slip

x

0.00 to

20.00

Hz

1.30

A

A

Q

Q

D

This setting is used as a reference value for the torque compensation function.

D

The default setting depends upon the Inverter capacity.

(The table shows the default settings for 400-V class, 200 kW Inverters.) (See page 8 - 42.)

D

Calculate the rated slip (E2-02) from the value shown on the motor nameplate with the following equa-

tion and set this value.

Rated slip = rated frequency (Hz) -- rated speed (r/min) × number of poles/120

J

Motor No-load Current: E2-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E2-03

Motor no-load current

x

0.00 to

2000.0

A

96.0

A

A

Q

Q

D

This setting is used as a reference value for the torque compensation function.

D

The default setting depends upon the Inverter capacity.

(The table shows the default settings for 400-V class, 200 kW Inverters.) (See page 8 - 42.)

D

Set the no-load current (E2-03) at the rated voltage and rated frequency. Normally this value isn’t shown

on the motor nameplate, so it might be necessary to contact the motor manufacturer.

7