3.7.4 Wiring PG Speed Control Card Terminal Blocks

3 - 22

3.7.4 Wiring PG Speed Control Card Terminal Blocks

Use no more than 100 meters of wiring for PG (encoder) signal lines, and keep them separate from power

lines.
Use shielded, twisted-pair wires for pulse inputs and pulse output monitor wires, and connect the shield to

the shield connection terminal.

J

Wire Sizes (Same for All Models)

Terminal wire sizes are shown in Table 3.7.

Table 3.7 Wire Sizes

Terminal

Terminal

Screws

Wire Thickness

(mm

2

)

Wire Type

Pulse generator power supply
Pulse input terminal
Pulse monitor output terminal

--

Stranded wire: 0.5 to

1.25
Single wire: 0.5 to 1.25

S

Shielded, twisted-pair wire

S

Shielded,

polyethylene-cov-

ered vinyl sheath cable

Shield connection terminal

M3.5

0.5 to 2

ered, vinyl sheath cable

J

Solderless Terminals for Control Circuit Terminals

The use of solderless terminals for the control circuit terminals is recommended because solderless termi-

nals are easy to connect securely.

Table 3.8 Straight Solderless Terminal Sizes

Wire Thickness

Model

d1

d2

Manufacturer

0.5 mm

2

A1 0.5-8 WH

1.00

2.60

0.75mm

2

A1 0.75-8 GY

1.20

2.80

Phoenix Contact

1 mm

2

A1 1-8 RD

1.40

3.00

Phoenix Contact

1.5 mm

2

A1 1.5-8 BK

1.70

3.50

d1 dia.

8 mm

14 mm

d2 dia.

Fig 3.16

Straight Solderless Terminal Sizes

Do not solder wires with the control circuit terminals if wires are used instead of solderless terminals.
Wires may not contact well with the control circuit terminals or the wires may be disconnected from the control

circuit terminals due to oscillation if the wires are soldered.