Advanced Operation

7.1.3 Setting/Adjusting Motor Constants

7 - 6

D

Fine-tune the gain when motor operation is unstable causing hunting to occur or torque/speed respon-

siveness is low.

When hunting occurs, increase the gain by 0.05 increments while checking the motor responsive-

ness.

When responsiveness is low, decrease the gain by 0.05 increments while checking the motor respon-

siveness.

7.1.3 Setting/Adjusting Motor Constants

J

Adjusting the V/f Pattern: E1-04 through E1-10, E1-13

Normally it isn’t necessary to adjust the V/f pattern with open-loop vector control. Adjust the V/f pattern

when you want to change the maximum output frequency setting or decrease the Inverter’s output voltage

or when stalls are occurring during no-load operation.
To increase the motor’s rated speed, increase the maximum output frequency in E1-04 in programming

mode after autotuning.
It is possible to make user-defined V/f pattern settings (E1-04 through E1-10) in open-loop vector control

mode. (The preset V/f patterns cannot be selected.)

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-04

Max. output frequen-

cy

x

50.0 to

150.0

Hz

60.0

Q

Q

Q

Q

E1-05

Max. voltage

x

0.0 to 510.0

*1

VAC 400.0

*1

Q

Q

Q

Q

E1-06

Base frequency

x

0.0 to 150.0

Hz

150.0

Q

Q

Q

Q

E1-07

Mid. output frequen-

cy

x

0.0 to 150.0

Hz

3.0

*2

Q

Q

A

x

E1-08

Mid. output frequen-

cy voltage

x

0.0 to 510.0

*1

VAC

22.0

*1, *2

Q

Q

A

x

E1-09

Min. output frequen-

cy

x

0.0 to 150.0

Hz

0.5

Q

Q

Q

A

E1-10

Min. output frequen-

cy voltage

x

0.0 to 510.0

*1

VAC

4.0

*1, *2

Q

Q

A

x

E1-13

Base voltage

x

0.0 to 510.0 VAC

0.0

A

A

Q

Q

* 1. These voltages are for 400-V Class Inverters; multiply the voltage by approx. 1.5 for 575-V

Class Inverters.

* 2. The default setting depends on the Inverter’s capacity. The default settings shown in the table

are for 400-V Class, 200 to 800 kW Inverters. (See page 8 - 42.)

Note 1.The default settings for E1-07 through E1-10 depend on the control method. The default

settings shown in the table are for open-loop vector control. (See page 8 - 41.)

2. The four frequency settings must satisfy the following formula:

E1-04 (F

MAX

) ≥ E1-06 (F

A

) > E1-07 (F

B

) ≥ E1-09 (F

MIN

)

3. When making the V/f characteristics a straight line, set the same value in E1-07 (middle

output frequency) and E1-09 (minimum output frequency). In this case, constant E1-08

(middle output frequency voltage) will be disregarded.

4. If E1-13 is set to 0.0, the same value as in E1-13 will be set for E1-05. It does not normally

need to be set separately.