8.2 Programming Mode Constants

8 - 43

J

575-V Class Inverters

Con-

stant

No.

Name

Unit

Factory Setting

--

Inverter Capacity

kW

300

600

900

1200

o2-04

kVA selection

1

91

92

93

94

C6-01

Carrier frequency upper limit *

kHz

2.0

2.0

2.0

2.0

--

Carrier frequency upper limit

range

kHz

2.0

2.0

2.0

2.0

C6-02

Carrier frequency lower limit

kHz

2.0

2.0

2.0

2.0

C6-03

Carrier frequency proportional

gain

1

0

0

0

0

E2-01

(E5-01)

Motor rated current

A

370.0

740.0

1110.0

1480.0

E2-02

(E5-02)

Motor rated slip

Hz

1.30

1.30

1.30

1.30

E2-03

(E5-03)

Motor no-load current

A

96.0

192.0

288.0

384.0

E2-05

(E5-05)

Motor line-to-line resistance

0.020

0.010

0.005

0.002

E2-06

(E5-06)

Motor leak inductance

%

5.0

5.0

5.0

5.0

L2-02

Momentary power loss ridethru

time

sec

1.0

1.0

1.0

1.0

L2-03

Min. baseblock time

sec

10.0

10.0

10.0

10.0

8