Setting the control method: a1-02 – Yaskawa G5HHP Drive User Manual

Page 92

Advertising
background image

Setting User Constants

4.2.5 Initialize Mode

4 - 24

J

Setting the Control Method: A1-02

D

Use constant A1-02 to select one of the four control methods.

D

This user constant is not returned to the factory setting when constants are initialized. It must be manual-

ly reset to the factory setting.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

A1-02

Control method selec-

tion

X

0 to 3

--

2

(Open Loop

Vector)

Q

Q

Q

Q

Control Method Settings

Setting

Function

0

V/f control without pulse generator (normal V/f control).

1

V/f control with PG feedback (V/f control using a PG Speed Control Card).

2

Open-loop vector control

(Vector control using the Inverter internal speed information).

3

Flux vector control

(Vector control using a PG Speed Control Card).

Changing the Control Method to Flux Vector

Use the following procedure to change the control method to select flux vector.

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

G5* Main Menu *

Operation

2

G5* Main Menu *

Initialize

3

DATA

ENTER

Select language

English

4

Press twice.

Control Method

Open Loop

5

DATA

ENTER

A1--02 = 2 ***

Open Loop

Changed to constant setting level.

6

A1--02 = 3

Flux Vector

7

DATA

ENTER

Entry Accepted

Writes-in the new setting.

Control Method

Flux Vector

After a few seconds, the Operator dis-

play is as shown on the left.

The control method has been changed to flux vector.

4

A

EXAMPLE

"