Basic Operation

6.1.1 Setting the Access Level and Control Method: A1-01, A1-02

6 - 2

6.1 Common Settings

This section describes the constants that are used with all of the control methods.

6.1.1 Setting the Access Level and Control Method: A1-01, A1-02

J

Constant Access Level: A1-01

D

Select the constant access level. This level determines which constants can be accessed and changed.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

A1-01

Constant access level

f

0 to 4

--

2 (Q)

Q

Q

Q

Q

D

Access Level Settings

Setting

Name

Function

0

Operation Only

Allows the operation mode and initialize mode to be displayed or

changed. Use this setting to prevent constant settings from being

changed.

1

User Program

Allows only the user-selected constants (up to 32) to be displayed or

changed. Set the desired constants as “User Parameters” in constants

A2-01 through A2-32.

2

Quick-Start

Allows the constants required to start the Inverter (about 25) to be dis-

played or changed.

3

Basic

Allows the commonly used constants to be displayed or changed.

4

Advanced

Allows all constants to be displayed or changed.

D

The control method setting also affects which constants can be displayed and changed. Refer to Chapter

8 User Constant Lists.

D

The constants required for basic operation can be displayed and changed in the Basic level, but this sec-

tion also describes constants that can be set only in the Advanced level, so set the access level to Ad-

vanced.

Changing the Access Level

The following procedure shows how to change from Quick-Start to Advanced.

Step

Key Sequence

Digital Operator Display

Remarks

1

MENU

G5* Main Menu *

Operation

Displays operation mode.

2

G5* Main Menu *

Initialize

Displays initialize mode.

3

DATA
ENTER

Select Language

English

Puts the Unit in initialize mode.

(Select Language display)

4

Access Level

Quick-Start

Displays the Access Level (A1-01).

5

DATA

ENTER

A1-01 = 2 ***

Quick-Start

Displays the constant setting for A1-01.

6

Depress Twice.

A1-01 = 4

Advanced

Displays Advanced.

7

DATA

ENTER

Entry Accepted

Writes the new setting.

Access Level

Advanced

Returns to the Access Level display.