Yaskawa G5HHP Drive User Manual

Page 256

Advertising
background image

Advanced Operation

7.5.6 Protective Functions: L

7 - 92

Table 7.13 Constants and Output Signals

Constant

Related output settings

Constant function

Speed Agree Level

(Absolute value)

Fref/Set Agree 1
Frequency Detection 1
Frequency Detection 2

Set the frequency (or motor speed) that you

want to detect in Hz.
The set speed is an absolute value, so the

speed is detected in forward or reverse.

Speed Agree Width

(Absolute value)

Fref/Fout Agree 1
Fref/Set Agree 1
Frequency Detection 1
Frequency Detection 2

Set the frequency (or motor speed) detec-

tion range in Hz.

Speed Agree Level

+/--

(Signed value)

Fref/Set Agree 2
Frequency Detection 3
Frequency Detection 4

Set the frequency (or motor speed) that you

want to detect in Hz.
Set positive values for forward, negative

values for reverse.

Speed Agree Width

+/--

(Signed value)

Fref/Fout Agree 2
Fref/Set Agree 2
Frequency Detection 3
Frequency Detection 4

Set the frequency(or motor speed) detec-

tion range in Hz.

D

Set the corresponding setting in the multi-function output (H2-01, H2-02, or H2-03) to output the de-

sired Fref/Fout Agree signal, Fref/Set Agree signal, or Frequency Detection signal.

Function

Setting

Fref/Fout Agree 1

2

Fref/Set Agree 1

3

Frequency Detection 1

4

Frequency Detection 2

5

Fref/Fout Agree 2

13

Fref/Set Agree 2

14

Frequency Detection 3

15

Frequency Detection 4

16

Frequency Detection Operation: L4-05

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L4-05

Operation when fre-

quency reference is

missing

x

0, 1

--

0

A

A

A

A

D

The frequency reference is considered lost when the frequency reference voltage drops by 90% for more

than 400 ms.

D

Settings

Setting

Function

0

Stop. (Operate according to the frequency reference value.)

1

Continue operation at 80% speed. (Continue operation with a speed that is 80% of the value

when the frequency reference was lost.)

7

Advertising