Advanced Operation

7.5.5 External Terminal Functions: H

7 - 78

During Run (Setting: 0)

OFF

The run command is OFF and there is not output voltage.

ON

The run command is ON or a voltage is being output.

During Run 2 (Setting: 37)

OFF

The Inverter is not outputting a frequency. (Baseblock, DC injection braking, initial excitation, or

stopped)

ON

The Inverter is outputting a frequency.

D

These outputs can be used to indicate the Inverter’s operating status.

Run command

Baseblock command

Output frequency

ON

ON

OFF

OFF

ON

OFF

ON

OFF

During run 1 output

During run 2 output

Fig 7.39

Timing Chart for “During RUN” Output

Zero-speed (Setting: 1)

OFF

The output frequency is greater than the minimum output frequency (E1-09).

(With flux vector control, motor speed is greater than the zero speed level (b2-01).)

ON

The output frequency is less than the minimum output frequency (E1-09).

(With flux vector control, motor speed is less than the zero speed level (b2-01).)

Output frequency

(Motor speed)

Minimum output frequency (E1-09)

(Zero speed level (b2-01) when flux vector control is

being used.)

Zero-speed output

OFF

ON

Fig 7.40

Timing Chart for Zero-speed

Motor Overload (OL1) Pre-alarm (Setting: 1F)

OFF

The motor protection function’s electronic thermal value is less than 90% of the detection level.

ON

The motor protection function’s electronic thermal value is greater than 90% of the detection

level.

D

This output function is valid when the motor overload protection function is enabled (L1-01 =1).

D

This output can be used to warn of overheating before the protection function itself operates.

Inverter Overheat (OH) Pre-alarm (Setting: 20)

OFF

The cooling fin temperature is less than the “OH Pre-Alarm Level” set in L8-02.

ON

The cooling fin temperature exceeds the “OH Pre-Alarm Level” set in L8-02.

D

This output function indicates that the temperature of the cooling fins reaches the temperature set in

L8-02 (the Inverter overheating alarm detection level).