5 torque limit function, Torque reference and torque limit, Stopping method – Yaskawa G5HHP Drive User Manual

Page 191

Advertising
background image

7.3 Flux Vector Control

7 - 27

J

Torque Reference and Torque Limit

If the torque reference has been assigned to a multi-function analog input or the frequency reference (cur-

rent) terminal, the input function changes when the control mode is switched between torque control and

speed control.

D

During speed control: The analog input terminal is used as the torque limit input.

D

During torque control: The analog input terminal is used as the torque reference input.

Either the absolute value of the torque limit input or the torque limit constant setting (L7-01 to L7-04),

whichever is smaller, will be used for the torque limit. Refer to 7.3.5 Torque Limit Function.

J

Stopping Method

D

When the run command is turned OFF during speed control, the motor is decelerated to a stop.

When the run command is turned OFF during torque control, the control mode is automatically switched

to speed control and the motor is decelerated to a stop.

D

When A1-02 is set to 3 (flux vector control), the speed/torque change command can be set for a multi-

function input (a setting of 71) to switch between speed and torque control during operation. An example

is shown below.

D

Settings

Terminal No.

User

Constant No.

Factor Setting

Setting

Function

16

H1-06

8

71

Speed/torque control change

36

b1-01

1

1

Frequency source (terminals 36, 39)

36

d5-03

1

1

Speed limit (terminals 36, 39)

42

H3-05

1

13

Torque reference/torque limit

Speed/torque change sig-

nal (terminal 16 input)

Run command

Control mode

Terminal 36 input

OPEN

CLOSED

Stop

Run

Speed

Torque

Speed (decel to stop)

Speed limit

Torque limit

Torque

reference

OPEN

CLOSED

Speed

Torque

Torque limit

Torque

reference

Speed

reference

Speed

reference

Speed limit

c

d

d

c

e

Terminal 42 input

Fig 7.13

Switching between Speed and Torque Control

7.3.5 Torque Limit Function

With flux vector control, the torque limit can be applied at an arbitrary value because the torque output by

the motor is calculated internally.

The torque limit function is useful when the load cannot sustain a torque above a certain level or regenerative

torque above a certain level.
The two ways to apply a torque limit are listed below.

D

Setting torque limits with the constants

D

Limiting torque with the analog inputs

The lower torque limit will be used if both of these methods are set. The accuracy of the torque limit is ±5%

at all frequencies.

7

Advertising