Advanced Operation

7.5.6 Protective Functions: L

7 - 96

D

L6-01/L6-04 Settings

Setting

Function

Display

0

Overtorque detection disabled

Overtorque detection 1

Overtorque output 2

1

Detect only during speed agree. Continue

operation even after detection. (Minor fault) “OL3” blinks

“OL4” blinks

2

Detect overtorque at any time. Continue op-

eration even after detection. (Minor fault)

“OL3” blinks

“OL4” blinks

3

Detect only during speed agree. Stop output

after detection. (Fault

)

“OL3” lights

“OL4” lights

4

Detect overtorque at any time. Stop output

after detection. (Fault)

“OL3” lights

“OL4” lights

D

When overtorque detection is enabled, be sure to set the overtorque detection level (L6-02 or L6-05)

and the overtorque detection time (L6-02 or L6-05). An overtorque condition is detected when the cur-

rent exceeds the overtorque detection level for longer than the overtorque detection time.

D

The overtorque detection level settings depend on the control method:

Open-loop or flux vector control: Set as a percentage of the motor rated torque.

Normal V/f or V/f with PG feedback control: Set as a percentage of the Inverter rated current.

D

Any of the following functions can be set in a multi-function output (H2-01, H2-02, or H2-03) to indi-

cate fact that an overtorque condition has been detected.

S

Setting B: Overtorque detection 1 (NO)

S

Setting 18: Overtorque detection 2 (NO)

S

Setting 17: Overtorque detection 1 (NC)

S

Setting 19: Overtorque detection 2 (NC)

Motor current

(Output torque)

L6-02 or L6-05

Overtorque Detection 1 (N.O.)

or Overtorque Detection 2

(N.O.)

ON

L6-03

or

L6-06

*

*

ON

L6-03

or

L6-06

* The overtorque detection is cleared when the current drops about 5% of the

Inverter’s rated current (or the motor’s rated torque).

Fig 7.47

Timing Chart for Overtorque Detection

J

Hardware Protection Settings: L8-01 to L8-03, L8-05, L8-07

Protection Selection for Internal DB Resistor: L8-01

Always set to 0 when using a Large-capacity Slim Type Inverter.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L8-01

Protect selection for

internal DB resistor

x

0, 1

--

0

B

B

B

B

D

Settings

7