2 programming mode constants, 1 application constants: b, Operation mode selections: b1 – Yaskawa G5HHP Drive User Manual

Page 270

Advertising
background image

User Constants

8.2.1 Application Constants: b

8 - 4

8.2 Programming Mode Constants

8.2.1 Application Constants: b

J

Operation Mode Selections: b1

C

t t

Name

S tti

F t

Change

Control Methods

Constant

Number

Display

Description

Setting

Range

Factory

Setting

Change

during

Opera-

tion

V/f

V/f

with

PG

Open

Loop

Vector

Flux

Vector

Page

b1-01

Reference selection

Used to set the input method for the

frequency reference.
0: Digital Operator
1: Control circuit terminals (ana-

0 to 3

1

x

Q

Q

Q

Q

6 - 4

b1-01

Reference Source

1: Control circuit terminals (ana-

log inputs).

2: Transmission
3: Option Card

0 to 3

1

x

Q

Q

Q

Q

6 4
6 - 7

b1-02

Operation method

selection

Used to set the source of the run

command.
0: Digital Operator
1: Control circuit terminals (se-

0 to 3

1

x

Q

Q

Q

Q

6 - 9

b1 02

Run Source

1: Control circuit terminals (se

quence inputs).

2: Transmission
3: Option Card

0 to 3

1

x

Q

Q

Q

Q

6 - 9

b1-03

Stopping method

selection

Used to set the stopping method

used when a stop command is in-

put.
0: Ramp to stop
1: Coast to stop.
2: DC injection braking stop:

(Stops faster than coast to stop,

0 to 3

0

x

Q

Q

Q

Q

6 - 12

b1 03

Stopping Method

(Stops faster than coast to stop,

no regenerative operation.)

3: Coast to stop with timer: Run

commands are disregarded dur-

ing deceleration.

;

Only settings 0 and 1 can be used

with flux vector control.

0 to 3

0

x

Q

Q

Q

Q

6 - 12

b1-04

Prohibition of reverse

operation

0: Reverse enabled
1: Reverse disabled

0, 1

0

x

B

B

B

B

6 - 11

b1 04

Reverse Oper

1: Reverse disabled

0, 1

0

x

B

B

B

B

6 - 11

b1-05

Operation selection

for setting of E1-09 or

less

Used to set the method of operation

when the frequency reference input

is less than the minimum output

frequency (E1-09).
0: Run at frequency reference

(E1-09 not effective).

1: STOP (Frequencies below

E1-09 in the coast to stop state.)

0 to 3

0

x

x

x

x

A

6 - 29

Zero-Speed Oper

E1-09 in the coast to stop state.)

2: Run at min. frequency. (E1-09)
3: Run at zero speed (Frequencies

below E1-09 are zero)

;

This function is only available in

with flux vector control.

b1-06

Read sequence input

twice

Used to set the responsiveness of

the control inputs (forward/reverse

and multi-function inputs.)
0: Two scans every 2 ms (Use

when connecting transistor out-

)

0, 1

1

x

A

A

A

A

6 - 9

b1 06

Cntl Input Scans

when connecting transistor out

puts.)

1: Two scans every 5 ms (Use

when connecting contact out-

puts or switches.)

0, 1

1

x

A

A

A

A

6 - 9

8

Advertising