Advanced Operation

7.3.3 Torque Control

7 - 20

Torque reference

Torque reference

primary delay filter

(d5-02)

+

+

+

Torque limit

(L7-01 to L7-04)

Torque compensation bias

Speed limit

Speed limiting circuit

Speed limit

bias (d5-05)

Speed feedback

Internal torque

reference

Fig 7.9

Torque Control Block Diagram

J

Torque Reference Settings: H3-04, H3-05, H3-08, H3-09

D

Set the multi-function analog input terminal 42 (H3-05) or 39 (H3-09) to torque reference (a setting of

13). The torque reference value cannot be set with the Digital Operator.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-05

Multi-function analog

input (terminal 42)

x

0 to 1F

--

0

B

B

B

B

H3-09

Multi-function analog

input (terminal 39)

x

1 to 1F

--

1F

A

A

A

A

D

Next, set the signal level for the analog input terminal that was set to torque reference.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-04

Signal level selection

(terminal 42)

x

0, 1

--

0

B

B

B

B

H3-08

Signal level selection

(terminal 39)

x

0 to 2

--

2

A

A

A

A

D

Signal Level Settings

Setting

Function

0

0 to +10 V input (When H3-08 is being set, be sure to disconnect jumper wire J1.)

1

0 to ±10 V input (When H3-08 is being set, be sure to disconnect jumper wire J1.)

2

4 to 20 mA input (H3-08 only)

D

Set the proper signal level for the torque reference that you want to input.

D

The direction of the torque that is output is determined by the sign (polarity) of the signal that was input.

It is not determined by the direction of the run command (forward/reverse).

+Voltage (or current):

Forward torque reference (generally counterclockwise; axis side)

--Voltage:

Reverse torque reference (generally clockwise; axis side)

Since the polarity of the voltage input determines the direction, only forward torque references can be

input when the “0 to +10 V” or “4 to 20 mA” signal level has been selected. If you want to input reverse

torque references, be sure to select the “0 to ±10 V” signal level.

7