Advanced Operation

7.5.2 Tuning Constants: C

7 - 52

Slip Compensation Selection During Regeneration: C3-04

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C3-04

Slip compensation

selection during re-

generation

x

0, 1

--

0

A

A

A

x

D

Settings

Setting

Contents

0

Slip compensation disabled during regeneration

1

Slip compensation enabled during regeneration

D

Constant C3-04 enables or disables slip compensation during regeneration.

D

The amount of regeneration is momentarily increased when this function is used, so some control option

(e.g., Braking resistor, Braking Resistor Unit, Braking Unit) may be required.

J

Torque Compensation Function: C4-01, C4-02

The torque compensation function detects increases in the motor load, and increases the output torque to

compensate.

Torque Compensation Gain: C4-01

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C4-01

Torque compensation

gain

x

0.00 to 2.50 Mul-

tiple

1.00

B

B

B

x

D

This constant can be changed during operation, but normally no adjustments are required. Make adjust-

ments in the following cases under the V/f control mode:

•

If the wiring distance between the Inverter and the motor is long, raise the setting.

•

If the motor capacity is less than the Inverter capacity (the maximum application motor capacity),

raise the setting.

•

If the motor generates excessive oscillation, lower the setting.

D

Set the torque compensation gain so that the output current at low-speed rotation does not exceed 50%

of the Inverter’s rated output current.

D

Do not adjust the setting of this constant for open-loop vector control.

Torque Compensation Time Constant: C4-02

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

C4-02

Torque compensation

time constant

x

0 to 10000

ms

20 *

A

A

A

x

* When the control method is switched, the factory setting changes as follows:

V/f control: 200; V/f with PG: 200; open-loop vector: 20

D

The torque compensation time constant does not normally need to be adjusted, but make adjustments

in the following cases:

•

If the motor generates excessive oscillation, raise the setting.

•

If motor responsiveness is low, lower the setting.