9.1 Protective and Diagnostic Functions

9 - 7

Corrective Actions

Probable causes

Meaning

Minor fault display

Excessive Speed Deviation

The load is too large.

Reduce the load.

DEV (blinking)

The speed deviation has been greater

than the setting in F1-10 for longer

than the setting in F1-11.

The acceleration time and deceleration

time are too short.

Lengthen the acceleration time and

deceleration time.

(

g)

Speed Deviation

than the setting in F1-11.

The load is locked.

Check the mechanical system.

The settings in F1-10 and F1-11 aren’t

appropriate.

Check the settings in F1-10 and F1-11.

UV4

PU Undervolt

PU Control Circuit Undervoltage
Module control power supply dropped

during operation.
400-V class: Detected only for

400 kW or larger Inverters.
575-V class: Detected only for

600 kW or larger Inverters.

---

S

Check wirings on the power supply

side.

S

Improve the power supply voltage.

UNBC

Unbalance Cur

Unbalanced Current
The output current for each Modulle

became unbalanced.
400-V class: Detected only for

400 kW or larger Inverters.
575-V class: Detected only for

600 kW or larger Inverters.

---

Check wirings.

OH4

Conv Ovr tmp

Converter overheating
The converter fin temperature became

higher than 105 °C.
400-V class: Detected only for

400 kW or larger Inverters.
575-V class: Detected only for

600 kW or larger Inverters.

---

Check the fin and ambient tempera-

tures.

EF3 (blinking)

External Fault 3

External fault (Input terminal 11)

EF4 (blinking)

External fault (Input terminal 12)

S

Reset external fault inputs to the

lti f

ti

i

t

EF5 (blinking)

External fault (Input terminal 13)

An “external fault” was input from a

multi-function input.

p

multi-function inputs.

S

Remove the cause of the external

EF6 (blinking)

External fault (Input terminal 14)

multi-function input.

S

Remove the cause of the external

fault.

EF7 (blinking)

External fault (Input terminal 15)

EF8 (blinking)

External fault (Input terminal 16)

CE

MEMOBUS Com Err

Communications Error
Normal reception was not possible for

2 s after received control data.

----

Check the communications devices

and signals.

BUS

Option Com Err

Option Card Transmission Error
A communications error occurred in a

mode where the run command or a

frequency reference is set from an

Transmission Option Card.

----

Check the Transmission Card and sig-

nals.

CALL

Serial Com Call

SI-B Communications Error
Control data was not normally re-

ceived when power was turned ON.

----

Check the communications devices

and signals.

E-15

Si-F/G Com Err

SI-F/G Communications Error De-

tected
A communications error occurred in a

mode where run or a frequency refer-

ence is set from an Transmission Op-

tion Card and E-15 is set to continue

operation.

----

Check the communications signals.

EF0

Opt External Flt

DDS/SI-B External Error Detected
An external error ware received from

an Option Card when EF0 was set to

continue operation.

----

Remove the cause of the external er-

ror.

9