3.7 Installing and Wiring PG Speed Control Cards

3 - 23

J

Closed-loop Connector Sizes and Tightening Torque

The closed-loop connectors and tightening torques for various wire sizes are shown in Table 3.9.

Table 3.9 Closed-loop Connectors and Tightening Torques

Wire Thickness [mm

2

]

Terminal

Screws

Crimp Terminal Size

Tightening Torque (N•m)

0.5

1.25 to 3.5

0.75

M3 5

1.25 to 3.5

0 8

1.25

M3.5

1.25 to 3.5

0.8

2

2 to 3.5

J

Wiring Method

Use the following procedure to connect wires to the terminal block.

1. Loosen the terminal screws with a thin-slot screwdriver.
2. Insert the wires from underneath the terminal block.
3. Tighten the terminal screws firmly.

Thin-slot screwdriver

Strip the end for

5.5 mm if no

solderless ter-

minal is used.

Solderless terminal or

wire without soldering

Control circuit

terminal block

Wires

3.5 mm max.

Blade thickness: 0.6 mm max.

Blade of screwdriver

Fig 3.17

Connecting Wires to Terminal Block