Advanced Operation

7.5.6 Protective Functions: L

7 - 90

Stall Prevention Selection During Decel: L3-04

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L3-04

Stall prevention selec-

tion during decel

x

0 to 2

--

1

B

B

B

B

D

Settings

Setting

Function

0

Disabled. (Decelerate according to the settings. Main circuit overvoltage may occur if the decel-

eration time is too short.)

1

Enabled. (Stops deceleration if the main circuit voltage exceeds the overvoltage level. Decelerate

again when voltage recovers.)

2

Optimum deceleration. (Decelerate as fast as possible judging from the main circuit voltage. Dis-

regard the deceleration time setting.)

D

When setting 1 (enabled) is selected, the deceleration time is extended automatically so that a main cir-

cuit overvoltage doesn’t occur.

D

Always select setting 0 when a braking option (Braking Resistor, Braking Resistor Unit, or Braking

Unit) is being used. If setting 1 or 2 is selected, the braking option won’t be used and the deceleration

time can’t be shortened.

D

L3-04 cannot be set to 2 for vector control modes.

The deceleration time is controlled

to prevent overvoltage.

Output frequency

Time

Deceleration time

(setting)

Fig 7.45

Deceleration Stall Prevention Function: L3-04 = 1

Stall Prevention Selection During Running: L3-05

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L3-05

Stall prevention selec-

tion during running

x

0 to 2

--

1

B

B

x

x

D

Settings

Setting

Function

0

Disabled. (Run according to the settings. Stalls may occur with large loads.)

1

Enabled -- deceleration time 1. (Use deceleration time in C1-02 for stall prevention function.)

2

Enabled -- deceleration time 2. (Use deceleration time in C1-04 for stall prevention function.)

D

When setting 1 or 2 (enabled) is selected, deceleration is started if the current of the stall prevention level

during operation continues for more than 100 ms. The motor is accelerated back to the reference fre-

quency again when the current falls below this level.