Advanced Operation

7.5.3 Reference Constants: d

7 - 54

7.5.3 Reference Constants: d

J

Frequency Reference Function: d2-01, d2-02

D

The frequency reference function sets the output frequency upper and lower limits.

D

When the frequency reference is zero and a run command is input, the motor operates at the frequency

reference lower limit (d2-02). The motor will not operate, however, if the lower limit is set lower than

the minimum output frequency (E1-09).

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

d2-01

Frequency reference

upper limit

x

0.0 to 110.0

%

100.0

B

B

B

B

d2-02

Frequency reference

lower limit

x

0.0 to 109.0

%

0.0

B

B

B

B

D

The frequency reference upper and lower limits are set as a percentage of the maximum output frequen-

cy (E1-04), in increments of 1%.

D

The upper and lower limits of the frequency reference are shown in Figure 7.27.

Set frequency reference

Internal frequency reference

Frequency reference

upper limit (d2-01)

Frequency reference

lower limit (d2-02)

Fig 7.27

Upper and Lower Limits of the Frequency Reference

J

Prohibited Frequencies (Jump Frequencies): d3-01 to d3-04

D

This function allows the prohibition or “jumping” of certain frequencies within the Inverter’s output

frequency range so that the motor can operate without resonant oscillations caused by some machine

systems.

D

It is also used for deadband control.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

d3-01

Jump frequency 1

x

0.0 to 150.0

Hz

0.0

B

B

B

B

d3-02

Jump frequency 2

x

0.0 to 150.0

Hz

0.0

B

B

B

B

d3-03

Jump frequency 3

x

0.0 to 150.0

Hz

0.0

B

B

B

B

d3-04

Jump frequency width

x

0.0 to 20.0

Hz

1.0

B

B

B

B

D

To disable this function, set the jump frequency references (d3-01 to d3-03) to 0.0 Hz.

D

For d3-01 to d3-03, set the center values of the frequencies to be jumped. Be sure to set the jump frequen-

cy so that d3-03 ≦ d3-02 ≦ d3-01.

D

For d3-04, set the jump frequency bandwidth. The jump frequency ± the jump frequency bandwidth

becomes the jump frequency range.

D

Operation is prohibited within the jump frequency range, but changes during acceleration and decelera-

tion are smooth with no jumps.

D

The relation between the internal frequency reference and the set frequency references is shown in Fig-

ure 7.28.

7