Basic Operation

6.4.2 Setting the Zero-speed Operation Constants

6 - 30

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b2-01

Zero speed level (DC

injection braking

starting frequency)

x

0.0 to 10.0

Hz

0.5

B

B

B

B

b2-03

DC injection braking

time at start

x

0.00 to

10.00

s

0.00

B

B

B

B

b2-04

DC injection braking

time at stop

x

0.00 to

10.00

s

0.50

B

B

B

B

D

With flux vector control, the DC injection braking function is replaced by the initial excitation function

and zero speed function.

D

The timing of the initial excitation function depends on the zero-speed operation method selected in

b1-05 (zero-speed operation), as shown in Figure 6.13.

D

The initial excitation function stops a motor that is rotating because of inertia.

Run command

OFF

ON

Frequency reference

from analog input

0

E1-09

D

b1-05 = 0

(RUN at Frequency

Ref)

Initial

excitation

BB (Baseblock)

BB

D

b1-05 = 1

(STOP)

Initial excitation

from E1-09

D

b1-05 = 2

(RUN at Min Frequency)

D

b1-05 = 3

(RUN at Zero RPM)

Zero speed

BB

BB

BB

BB

BB

BB

Zero speed

Inverter internal frequency reference

(Soft start input)

After the frequency reference

falls below E1-09, initial excita-

tion starts when the motor speed

drops below b2-01.

After the run command goes

OFF, zero-speed control is

performed for the time set in

b2-04 when the motor speed

drops below b2-01.

After the run command goes

OFF, zero-speed control is

performed for the time set in

b2-04 when the motor

speed drops below b2-01.

Initial

excitation

Initial

excitation

After the run command goes

OFF, zero-speed control is per-

formed for the time set in b2-04

when the motor speed drops be-

low b2-01.

Fig 6.13

Settings for Initial Excitation and Zero-speed Control

D

Initial excitation is started from b2-01 (zero speed level) when decelerating. A setting of b2-01 < E1-09

is valid only with flux vector control.

D

The current level for the initial excitation function is set in E2-03 (motor no-load current).

D

The DC injection braking current (b2-02) isn’t used with flux vector control and can’t be set.