6.2.1 Autotuning

6 - 18

6.2 Open-loop Vector Control

Open-loop vector control is vector control without a pulse generator input. Autotuning is the only setting for ba-

sic operation with open-loop vector control.

Always perform autotuning for motor unit separately before vector control operation.
To operate with the greatest speed precision near the rated speed, select a motor with a rated voltage that is at

least 40 V below the Inverter’s input power supply voltage for 400-V Class Inverters and 60 V below for 575-V

Class Inverters. When the input voltage is the same as the rated voltage, the voltage limit may be applied and

vector control won’t be established.

6.2.1 Autotuning

CAUTION

D

Do not connect a load to the motor when performing autotuning.

Doing so may result in personal injury or equipment damage.
When motor cannot be disconnected from the load, motor constantscan be setby calculation. Contact your

YASKAWA representatives for details.

J

Precautions before Autotuning

D

The Inverter’s autotuning function automatically determines the motor constants while a servo system’s

autotuning function determines the size of a load, so these autotuning functions are fundamentally dif-

ferent.

D

If a load is connected when autotuning is performed, not only will incorrect motor constants be recorded,

but the motor may operate erratically or unexpectedly. Disconnect the load before autotuning.

D

The motor shaft with rotate when autotuning is performed. Confirm safety before starting autotuning.

D

When motor cannot disconnected from the load, motor constants can be set by calculation. Contact your

YASKAWA representatives for details.

J

Inverter Input Voltage Setting: E1-01

D

Set the Inverter input voltage (E1-01) to match the power supply voltage.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-01

Input voltage setting

x

360 to

460(460 to

690)

VAC

400

(600)

Q

Q

Q

Q

D

The voltage settings shown in parentheses are the values for the 575-V class. This setting is used as the

reference value for functions such as the protection functions.

J

Required Constant Settings

1. Enter autotuning mode and make the following constant settings:

Rated Voltage

Set the rated voltage (VAC) shown on the motor nameplate.

Rated Current

Set the rated current (A) shown on the motor nameplate.

Rated Frequency

Set the rated frequency (Hz) shown on the motor nameplate.

Rated Speed

Set the rated speed (r/min) shown on the motor nameplate.

Number of Poles

Set the number of poles.

Motor Selection

Select motor 1 or motor 2. (Normally select motor 1.)

2. The following message will appear when the constants have been set:

Tuning Ready?

Press RUN Key

The “Press RUN Key” message will

blink.