Yaskawa G5HHP Drive User Manual

Page 192

Advertising
background image

Advanced Operation

7.3.5 Torque Limit Function

7 - 28

J

Setting a Torque Limit with Constants: L7-01 to L7-04

D

Torque limits can be set separately for the 4 ways that torque can be applied: forward torque, reverse

torque, forward regenerative torque, and reverse forward regenerative torque.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

L7-01

Forward torque limit

x

0 to 300

%

200

x

x

B

B

L7-02

Reverse torque limit

x

0 to 300

%

200

x

x

B

B

L7-03

Forward regenerative

torque limit

x

0 to 300

%

200

x

x

B

B

L7-04

Reverse regenerative

torque limit

x

0 to 300

%

200

x

x

B

B

D

Figure 7.14 shows the relationship between each constant and the output torque.

L7-04

L7-01

L7-02

L7-03

Output torque

Forward

direction

Reverse

direction

Motor speed

Reverse

Forward

Regenerative

torque

Regenerative

torque

Fig 7.14

Torque Limit Function

D

When the torque limit function is used, the torque control has priority and motor speed control and com-

pensation will be disregarded, so the acceleration/deceleration times might be lengthened and motor

speed might be reduced.

J

Limiting Torque with Analog Inputs: H3-05, H3-09

The following two analog inputs that can be used to limit torque. Use either or both of these inputs as needed

with constants H3-05 and H3-09.

D

Multi-function analog input terminal 42

D

Frequency reference (current) terminal 39

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-05

Multi-function analog

input (terminal 42)

x

0 to 1F

--

0

B

B

B

B

H3-09

Multi-function analog

input (terminal 39)

x

1 to 1F

--

1F

A

A

A

A

D

Settings

Setting

Name

10

Forward Torque Limit

11

Reverse Torque Limit

12

Regenerative Torque Limit

13

Torque reference (The input limits torque in both the forward and reverse directions during speed

control.)

15

Forward/Reverse Torque Limit (Limits torque in both the forward and reverse directions.)

D

The above table shows only those settings related to the torque limit function.

D

Set the analog input terminal’s signal level, gain, and bias to match the actual input signal.

7