7.5 Common Functions

7 - 49

D

Reducing Long-cycle Oscillation

If oscillation occurs with a longer cycle than the integral time (I) setting, it means that integral operation

is strong. The oscillation will be reduced as the integral time (I) is lengthened.

After adjustment

Before adjustment

Response

Time

D

Reducing Short-cycle Oscillation

If the oscillation cycle is short and oscillation occurs with a cycle approximately the same as the deriva-

tive time (D) setting, it means that the derivative operation is strong. The oscillation will be reduced as

the derivative time (D) is shortened.
If oscillation cannot be reduced even by setting the derivative time (D) to “0.00” (no derivative control),

then either lower the proportional gain (P) or raise the PID primary delay time constant.

After adjustment

Before adjustment

Response

Time

J

Dwell Functions: b6-01 to b6-04

D

The dwell functions are used to temporarily hold the output frequency when starting or stopping a motor

with a heavy load. This helps to prevent stalling.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b6-01

Dwell frequency at

start

x

0.0 to 150.0

Hz

0.0

A

A

A

A

b6-02

Dwell time at start

x

0.0 to 10.0

s

0.0

A

A

A

A

b6-03

Dwell frequency at

stop

x

0.0 to 150.0

Hz

0.0

A

A

A

A

b6-04

Dwell time at stop

x

0.0 to 10.0

s

0.0

A

A

A

A

D

The relation between these constants is shown in Figure 7.23.

Output

frequency

b6-02

b6-01

b6-04

Time

b6-03

Run command

OFF

ON

Fig 7.23

Timing Chart for Dwell Functions