6.4 Flux Vector Control

6 - 29

6.4.2 Setting the Zero-speed Operation Constants

D

With flux vector control, operation is possible even when the frequency reference is zero (below the

minimum output frequency).

D

Set the operation methods for the minimum output frequency.

J

Stopping Method Selection: b1-03

D

Set the stopping method used when a stop command is input.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b1-03

Stopping method

selection

x

0 to 3

--

0

Q

Q

Q

Q

D

Settings

Setting

Function

0

Deceleration to stop

1

Coast to stop

2

DC injection braking stop (This setting can’t be made with flux vector control.)

3

Coast to stop with timer (This setting can’t be made with flux vector control.)

J

Zero-speed Operation: b1-05 and Minimum Output Frequency: E1-09

D

Set the operation method used when the frequency reference is below the minimum output frequency.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

b1-05

Operation selection

for setting of E1-09 or

less

x

0 to 3

--

0

x

x

x

A

D

Settings

Setting

Function

0

Operate according to the frequency reference. (E1-09 is invalid.)

1

Interrupt the output. (Coast when the frequency reference is below E1-09.)

2

Operate at E1-09 frequency. (Output the frequency set in E1-09.)

3

Zero-speed operation (Zero reference value when the frequency reference is below E1-09.)

Minimum Output Frequency (FMIN): E1-09

D

Set the minimum output frequency according to the requirements of the application.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-09

Min. output frequency

x

0.0 to 150.0

Hz

0.0

Q

Q

Q

A

J

Initial Excitation Settings: b2-01, b2-03, b2-04

D

Set the zero speed level, DC injection braking time at startup, and the DC injection braking time when

stopping.