Basic Operation

6.3.2 V/f Pattern Selection: E1-03

6 - 22

6.3.2 V/f Pattern Selection: E1-03

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-03

V/f pattern selection

x

0 to F

--

F

Q

Q

x

x

D

The V/f pattern can be set to any of the following:

One of 15 preset patterns (settings 0 through E)

A custom user-set pattern (setting F)

D

The factory setting for E1-03 is “F” (user-defined V/f pattern), but the default contents of this setting

are the same as setting “1.”

J

Selecting a Preset V/f Pattern: E1-03 = “0” through “E”

D

Refer to the following table to set one of the 15 preset patterns.

Characteristics

Applications

Setting

Specifications

These patterns are for general-purpose

applications

0

50 Hz

Fixed torque

p

g

p p

applications.
Use these patterns when the load torque

1

60 Hz

Fixed torque

Use these patterns when the load torque

is to remain constant for any rotational

speed such as in straight-line convey-

2

60 Hz, Voltage saturation at 50 Hz

speed, such as in straight-line convey-

ors.

3

72 Hz, Voltage saturation at 60 Hz

U th

tt

h

th

i

4

50 Hz, cubic

Variable torque

Use these patterns when there is a qua-

dratic or cubic relationship between the

5

50 Hz, quadratic

Variable torque

dratic or cubic relationship between the

rotational speed and load, such as in fans

or pumps

6

60 Hz, cubic

or pumps.

7

60 Hz, quadratic

Select a high starting torque V/f pattern

only in the following cases:

S

The wiring distance between the In-

8

50 Hz, low starting torque

High starting

S

The wiring distance between the In-

verter and motor is relatively large

(greater than 150 m).

S

A large torque is required at startup

9

50 Hz, high starting torque

High starting

torque*

S

A large torque is required at startup

(such as for heavy axis loads).

S

An AC or DC reactor is connected to

the Inverter’s input or output

A

60 Hz, low starting torque

the Inverter’s input or output.

S

A motor less than the maximum appli-

cable motor is being used.

b

60 Hz, high starting torque

Hi h

d

These patterns are for applications that

f

i

h

C

90 Hz, Voltage saturation at 60 Hz

High-speed op-

eration

These patterns are for applications that

must rotate at frequencies greater than

60 Hz. A fixed voltage is applied at fre-

d

120 Hz, Voltage saturation at 60 Hz

eration

60 Hz. A fixed voltage is applied at fre-

quencies greater than 60 Hz.

E

150 Hz, Voltage saturation at 60 Hz

* Normally it isn’t necessary to use these patterns because starting torque isensured byautomatic

torque boost functions.

D

The constant settings for E1-04 through E1-10 will be changed automatically when one of these patterns

is selected.

D

The characteristics for these patterns are shown in the diagrams on the following page.