7.5 Common Functions

7 - 83

Output voltage

Gain × 10 V

10 V

0 V

Monitored item

0 %

100 %

Bias × 100

10 V

Fig 7.41

Monitor Output Adjustments

Multi-function Analog Output Signal Level: H4-07

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H4-07

Analog output signal

level selection

x

0, 1

--

0

B

B

B

B

D

Settings

Setting

Function

0

0 to +10 V (Absolute value output)

1

0 to

±

10 V

D

This signal level setting applies to analog outputs 1 and 2 (terminals 45 and 48).

D

When the 0 to ±10 V signal level is used to output speed values (frequency reference, output frequency,

or motor speed), positive voltage indicates Inverter output in the forward direction and negative voltage

indicates Inverter output in the reverse direction. (Assuming a bias setting of 0.0.)

D

There are some monitor items that are limited to the 0 to +10 V signal range even when the 0 to ±10 V

signal level has been selected. Refer to Table 4.3 Status Monitor Items for details.

J

MEMOBUS Communications Settings: H5-01 to H5-05

Station Node Address: H5-01

D

Set the Inverter node address.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H5-01

Station address

x

0 to 20

--

1F

A

A

A

A

Baud Rate: H5-02

D

Set the baud rate for MEMOBUS communications.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H5-02

Communication speed

selection

x

0 to 3

--

3

A

A

A

A

D

Settings

Setting

Baud Rate

0

1200 bps

1

2400 bps;

2

4800 bps

3

9600 bps

7