7.3 Flux Vector Control

7 - 29

D

The factory default settings for the input terminal’s signal level are as follows:

Terminal 42: 0 to +10 V (A 10 V input limits the torque to 100% of the motor’s rated torque.)

Terminal 39: 4 to 20 mA (A 20 mA input limits the torque to 100% of the motor’s rated torque.)

Figure 7.15 shows the relationship between the output torque and each torque limit.

Output torque

Forward

direction

Reverse

direction

Regenerative torque limit

Reverse torque limit

Motor speed

Reverse

Forward

Forward torque limit

Regenerative torque limit

Fig 7.15

Limiting Torque via Analog Inputs

D

When the forward torque limit has been set, the analog input signal acts as the limit value for torque

generated in the forward direction. The torque limit input is effective when torque is generated in the

forward direction even if the motor is operating in reverse (regenerative torque).

D

The torque limit is 100% of the motor’s rated torque when the analog input is at its maximum value (10

V or 20 mA). To increase the torque limit above 100%, set the input terminal’s gain above 100%. For

example, a gain of 150.0% would result in a torque limit of 150% of the motor’s rated torque with a 10

V or 20 mA analog input.

7.3.6 Setting/Adjusting Motor Constants

J

Adjusting the V/f Pattern: E1-04 to E1-07, E1-13

D

Normally it isn’t necessary to adjust the V/f pattern with flux vector control. Adjust the V/f pattern when

you want to change the maximum output frequency, maximum voltage, base frequency, or minimum

output frequency settings.

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

E1-04

Max. output frequen-

cy

x

50.0 to

150.0

Hz

60.0

Q

Q

Q

Q

E1-05

Max. voltage

x

0.0

to

510.0

*1

VAC

400.0

*1

Q

Q

Q

Q

E1-06

Base frequency

x

0.0 to 150.0

Hz

60.0

Q

Q

Q

Q

E1-09

Min. output frequen-

cy

x

0.0 to 150.0

Hz

0.0

Q

Q

Q

A

E1-13

Base voltage

x

0.0 to 510.0 VAC

0.0

*2

A

A

Q

Q

* 1. These voltages are for the 400-V Class Inverters; multiply the voltage by approx. 1.5 for

575-V Class Inverters.

* 2. If E1-13 is set to 0.0, the same value as in E1-13 will be set for E1-05. It does not normally

need to be set separately.

Note 1.The default setting for E1-09 depends on the control method. The default settings shown

in the table are for flux vector control.

2. The three frequency settings must satisfy the following equation:

E1-04 (F

MAX

) ≥ E1-06 (F

A

) > E1-09 (F

MIN

)

7