Advanced Operation

7.3.3 Torque Control

7 - 22

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

H3-01

Signal level selection

(terminal 36)

x

0, 1

--

0

B

B

B

B

D

Setting (See page 6 - 4.)

Setting

Function

0

0 to 10 VDC input

1

--10 to 10 VDC input

(A negative voltage is a command for rotation in the opposite direction.)

D

Set the signal level to match the speed limit voltage being input.

D

Limit with Constant Setting (d5-03 = 2)

User

Change

during

Setting

Factory

Valid Access Levels

User

Constant

Number

Name

g

during

Opera-

tion

Setting

Range

Unit Factory

Setting

V/f

Control

V/f with

PG

Open

Loop

Vector

Flux

Vector

d5-04

Speed limit

x

--120 to

+120

%

0

x

x

x

A

Set the speed limit as a percentage of the maximum frequency. (The max. frequency is 100%.) The

sign of the constant setting and the direction of the run command determine the direction in which

the speed is limited.

Setting +: Forward rotation; Speed is limited in the forward direction.

Reverse rotation; Speed is limited in the reverse direction.

Setting --: Forward rotation; Speed is limited in the reverse direction.

Reverse rotation; Speed is limited in the forward direction.

The speed limit value is zero for rotation opposite to the speed limit direction.

For example, when a positive value is set in d5-04 and the forward rotation command is ON, the

effective range of the torque control is from zero to the speed limit value in the forward direction

(when constant d5-05, the speed limit bias, is set to 0).