8.2 Programming Mode Constants

8 - 27

* The values in parentheses indicate initial values when initialized in 3-wire sequence.

Multi-function Input Functions

Control Methods

Setting

value

Function

V/f

V/f

w/

PG

Open

loop

Vector

Flux

vector

Page

0

3-wire sequence (Forward/Reverse run command)

f

f

f

f

6 - 14

1

Local/Remote selection (ON: Operator, OFF: Constant setting)

f

f

f

f

7 - 63

2

Option/Inverter selection (ON: Option card)

f

f

f

f

7 - 63

3

Multi-step speed reference 1
When H3-05 is set to “0,” this function is combined with “Master/auxiliary speed switch.”

f

f

f

f

6 - 14

4

Multi-step speed reference 2

f

f

f

f

6 - 14

5

Multi-step speed reference 3

f

f

f

f

6 - 14

6

Jog frequency reference (higher priority than multi-step speed reference)

f

f

f

f

6 - 14

7

Accel/Decel time 1

f

f

f

f

6 - 17

8

External baseblock NO (NO contact: Baseblock at ON)

f

f

f

f

7 - 64

9

External baseblock NC (NC contact: Baseblock at OFF)

f

f

f

f

7 - 64

A

Accel/Decel ramp hold (ON: Accel/decel stopped, frequency on hold)

f

f

f

f

7 - 64

B

OH2 alarm signal input (ON: OH2 will be displayed)

f

f

f

f

7 - 65

C

Multi-function analog input selection (ON: Enable)

f

f

f

f

7 - 65

D

No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f control)

f

f

x

x

7 - 65

E

Speed control integral reset (ON: Integral control disabled)

x

f

x

f

7 - 65

F

Not used. (Do not input this setting.)

--

--

--

--

--

10--

Up command (Always set with the down command)

f

f

f

f

7 - 67

11

Down command (Always set with the up command)

f

f

f

f

7 - 67

12

FJOG command (ON: Forward run at jog frequency d1-09)

f

f

f

f

6 - 17

13

RJOG command (ON: Reverse run at jog frequency d1-09)

f

f

f

f

6 - 17

14

Fault reset (Reset when turned ON)

f

f

f

f

7 - 68

15

Emergency stop (ON: Deceleration to stop in emergency stop time C1-09)

f

f

f

f

6 - 17

16

Motor switch command (Motor 2 selection)

f

--

f

--

7 - 68

18

Timer function input (Functions are set with b4-01, b4-02 and the timer function is set at the

same time)

f

f

f

f

7 - 43

19

PID control disable (ON: PID control disabled)

f

f

f

f

7 - 69

1A

Accel/Decel time 2

f

f

f

f

6 - 17

1B

Constants write enable (ON: All constants can be written-in. OFF: All constants other than fre-

quency monitor are write protected.)

f

f

f

f

7 - 69

1C

Trim control increase (ON: d4-02 frequencies are added to analog frequency references.)

f

f

f

f

7 - 69

1D

Trim control decrease (ON: d4-02 frequencies are subtracted from analog frequency references.)

f

f

f

f

7 - 69

1E

Analog frequency reference sample/hold

f

f

f

f

7 - 71

1F

Frequency reference terminal 36/39 selection (ON: selects terminal 39)

f

f

f

f

6 - 17

20 to 2F

External fault (Desired settings possible)
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
Stopping method: Deceleration to stop, coast to stop, emergency stop or continue operation.

f

f

f

f

7 - 71

30

PID control integral reset (ON: Reset)

f

f

f

f

--

60

DC injection braking command (ON: Performs DC injection braking)

f

f

f

f

7 - 74

61

External speed search command 1: Maximum output frequency (ON: speed search)

f

x

f

x

7 - 74

62

External speed search command 2: Set frequency (ON: speed search)

f

x

f

x

7 - 74

63

Energy-saving command (ON: Energy-saving control set for b8-01, b8-02)

f

f

x

x

7 - 12

8