5.2 Trial Operation Procedures

5 - 13

D

Be sure to tighten all the screws when securing the motor shaft to the mechanical system.

J

Operation using the Digital Operator

D

Use the Digital Operator in the same way as in no-load operation.

D

If fault occurs during operation, make sure the STOP Key on the Digital Operator is easily accessible.

D

At first, set the frequency reference to a low speed of one tenth the normal operating speed.

J

Checking Operating Status

D

Having checked that the operating direction is correct and that the machine is operating smoothly at slow

speed, increase the frequency reference.

D

After changing the frequency reference or the rotation direction, check that there is no oscillation or ab-

normal sound from the motor. Check the monitor display to ensure that the U1-03 (output current) is

not excessive.