Fw-1007, Fw-1008, Fw-1009 – Dell POWEREDGE M1000E User Manual

Page 462

Advertising
background image

440

Fabric OS Message Reference

53-1002749-01

FW-1007

5

FW-1007

Message

<Label>, is above high boundary(High=<High value>, Low=<Low value>). Current value
is <Value> <Unit>.

Message Type

LOG

Severity

WARNING

Probable Cause

Indicates that the speed of the fan has risen above the high boundary. Fan problems typically contribute
to temperature problems.

Recommended

Action

Consistently abnormal fan speeds generally indicate that the fan is failing. Replace the fan
field-replaceable unit (FRU).

FW-1008

Message

<Label>, is between high and low boundaries(High=<High value>, Low=<Low value>).
Current value is <Value> <Unit>.

Message Type

LOG

Severity

INFO

Probable Cause

Indicates that the speed of the fan has changed from a value outside of the acceptable range to a value
within the acceptable range. Fan problems typically contribute to temperature problems.

Recommended

Action

No action is required. Consistently abnormal fan speeds generally indicate that the fan is failing. If this
message occurs repeatedly, replace the fan field-replaceable unit (FRU).

FW-1009

Message

<Label>, value has changed(High=<High value>, Low=<Low value>). Current value is
<Value> <Unit>.

Message Type

LOG

Severity

INFO

Probable Cause

Indicates that the state of the power supply has changed from faulty to functional or from functional to
faulty.

Recommended

Action

If the power supply is functioning correctly, no action is required.

If the power supply is functioning below the acceptable boundary, verify that it is seated correctly in the
chassis. Run the psShow command to view the status of the power supply. If the power supply continues
to be a problem, replace the faulty power supply.