Hil-1104, Hil-1105, Hil-1106 – Dell POWEREDGE M1000E User Manual

Page 571

Advertising
background image

Fabric OS Message Reference

549

53-1002749-01

HIL-1104

5

HIL-1104

Message

Blower <blower number> faulted, <nominal voltage> (<measured voltage>) is below
threshold.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the fan voltage is below threshold.

Recommended

Action

Run the psShow command to verify the power supply status.

Try to reseat the faulty fan field-replaceable units (FRUs) and power supply FRU to verify that they are
seated properly.

If the problem persists, replace the fan FRU or the power supply FRU as necessary.

HIL-1105

Message

Switch error, <nominal voltage> (<measured voltage>) above threshold.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the switch voltage is above threshold. This message is specific to non-bladed switches.

Recommended

Action

For switches that do not have field-replaceable units (FRUs), replace the entire switch.

If the 12 volt level is faulty, replace one or both power supplies; if any other voltage is faulty, replace the
entire switch.

HIL-1106

Message

Switch error, <nominal voltage> (<measured voltage>) below threshold.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the switch voltage is below threshold. This message is specific to non-bladed switches.

Recommended

Action

For switches that do not have field-replaceable units (FRUs), replace the entire switch.

If the 12 volt level is faulty, replace one or both power supplies; if any other voltage is faulty, replace the
entire switch.