Fabric OS Message Reference

53-1002749-01

HIL-1311

5

Recommended

Action

Because the fans are not field-replaceable, replace the switch if the temperature is high.

HIL-1311

Message

No fans are faulty.

Message Type

LOG

Severity

INFO

Probable Cause

Indicates recovery from an earlier condition of one or more fans having failed.

Recommended

Action

This can only occur on switches with non-removable fans. It follows a previous indication of faultiness.

If the fan continues to generate this message, it indicates oscillation between faulty and non-faulty
behavior. Replace the switch because the fan is not field-replaceable.

HIL-1401

Message

One fan FRU missing. Install fan FRU immediately.

Message Type

LOG

Severity

WARNING

Probable Cause

Indicates that a fan field-replaceable unit (FRU) has been removed.

Recommended

Action

Install the missing fan FRU.

HIL-1402

Message

Two fan FRUs missing. Install fan FRUs immediately.

Message Type

LOG

Severity

WARNING

Probable Cause

Indicates that two fan field-replaceable units (FRUs) have been removed.

Recommended

Action

Install the missing fan FRUs immediately.