552

Fabric OS Message Reference

53-1002749-01

HIL-1206

5

HIL-1206

Message

Fan <fan number> sensor <sensor number> , speed (<measured speed> RPM) below
threshold.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the specified fan speed (in RPM) has fallen below the minimum threshold. This problem
can quickly cause the switch to overheat. This message is specific to non-bladed switches.

Recommended

Action

Replace the fan field-replaceable unit (FRU).

HIL-1207

Message

Fan <fan number> is faulty.

Message Type

LOG

Severity

ERROR

Probable Cause

Indicates that the fan is faulty.

Recommended

Action

Use the tempShow command to verify that the switch temperatures are within operational ranges. Refer
to the hardware reference manual for the temperature range of your switch.

Make sure that the area is well-ventilated and that the room temperature is within the operational range
of your switch. Refer to the hardware reference manual for your switch for the operational temperature
range.

Use the fanShow command to monitor the status of the fan generating this error.

If the fan continues to generate this message, replace the switch because the fan is not field-replaceable.

HIL-1208

Message

Fan <fan number> is not faulty.

Message Type

LOG

Severity

INFO

Probable Cause

Indicates that the fan is not faulty.

Recommended

Action

This can only occur on switches with non-removable fans. It follows a previous indication of faultiness.

If the fan continues to generate this message, it indicates oscillation between faulty and non-faulty
behavior. Replace the switch because the fan is not field-replaceable.