Fw-1445, Fw-1446 – Dell POWEREDGE M1000E User Manual

Page 546

Advertising
background image

524

Fabric OS Message Reference

53-1002749-01

FW-1445

5

Recommended

Action

Replace the FRU.

FW-1445

Message

Four power supplies are now required for 2X redundancy, Switch Status Policy
values changed.

Message Type

LOG

Severity

INFO

Probable Cause

Indicates that the switch requires four power supplies and the prior Switch Status Policy parameters will
be overwritten to reflect this. The presence of an AP blade means that more than one power supply may
be required to provide adequate power. So (even if the AP blade is powered down or removed) the
Switch Status Policy values will now reflect the need for four power supplies to maintain full (2X)
redundancy.

Recommended

Action

No action required unless there are fewer than four power supplies active in the chassis. If there are
fewer than four, insert additional power supplies so that there are four active power supplies.

FW-1446

Message

Four power supplies now required for 2X redundancy, not enforced by Fabric Watch
due to Switch Status Policy overridden by User.

Message Type

LOG

Severity

WARNING

Probable Cause

Indicates that the switch now requires four power supplies for full (2X) redundancy, but the user has
previously overridden the Switch Status Policy values pertaining to the number of power supplies. So
those values will not be automatically changed.

With no AP blades, the default value is 3 (out of service), indicating switch status is down or 0 indicating
no checking for switch status marginal.

When an AP blade is or has been present, the default value is 2 (out of service) indicating switch status
is down or 1 (out of service) indicating switch status is marginal.

Recommended

Action

To maintain full (2X) redundancy and proper monitoring by Fabric Watch, supply four active power
supplies and enter the default values associated with the presence of an AP blade using the
switchStatusPolicySet command.