Fabric OS Message Reference

53-1001767-01

EM-1036

22

Probable Cause

Suggests that since both power supplies associated with one of the two main circuits are present
but faulty, maybe the circuit's switch has been turned off, or the AC power source has been
interrupted for that circuit.

The Switch side value is either "left" or "right" designating which circuit switch, facing the cable side
of the chassis. The Switch side value indicates:

left: controls the odd numbered power supply units.

right: controls the even numbered power supply units.

Recommended

Action

Check that the identified AC circuit switch is turned on, that the power cord is properly attached
and undamaged, and that the power source is operating properly.

Severity

ERROR

EM-1036

Message

<timestamp>, [EM-1036], <sequence-number>,, WARNING, <system-name>,

<FRU Id>

is

not accessible.

Probable Cause

Indicates that the specified field-replaceable unit (FRU) does not seem to be present on the switch.

If the FRU is a world wide name (WWN) card, then default WWN and IP addresses are used for the
switch.

Recommended

Action

Reseat the FRU card.

If the message persists, reboot or power cycle the switch.

Run the systemVerification command to verify that the switch does not have hardware problems. To
run this command root access is required. Refer to the Fabric OS Command Reference for more
information on this command.

If the message persists, replace the FRU.

Severity

WARNING

EM-1037

Message

<timestamp>, [EM-1037], <sequence-number>,, INFO, <system-name>,

<FRU Id>

is no

longer faulted.

Probable Cause

Indicates that the specified power supply has been marked as no longer being faulty, probably
because its AC power supply has been turned on.

Recommended

Action

No action is required.

Severity

INFO