Yaskawa SGDB User Manual

Page 121

Advertising
background image

3.4 Setting Stop Mode

109

When using the holding brake, turn ON and OFF the brake with the following timing be-
cause a delay occurs. The brake interlock is useful for adjusting the timing.

OFF

OFF

OFF

OFF

SERVOPACK

control power supply

SERVOPACK

main power supply

Servo ON

Holding brake power supply

Brake contact part
(Lining)

Speed reference

Open

Motor rotation

ON

ON

ON

ON

*1

*2

*4

*5

*6

*3

200ms or more

200ms to 1.0 s

0V

t

0

+t

1

t

1

t

0

*2

* 1 Apply the holding brake at the same time as the Servo ON.
* 2 The mechanical contact takes 180 ms max. to be opened when the brake is turned ON and 100 ms max. to be closed when turned

OFF.

* 3 Allow 200 ms or more between the moment when the brake is turned ON and when the speed reference is input.
* 4

t

o

indicates the motor stopping time. The table below shows the fomula.

* 5 Do not turn OFF the brake power supply before the motor stops. Normally,

t

o

+

t

1

is approx. 1 to 2 seconds.

* 6 In 0.2 to 1.0 seconds after turning OFF the brake power supply, turn OFF the servo ON.

Using SI Units

Using Gravitational Units

(s)

(J + J ) × N

M

L

M

(T + T )

P

L

t =

o

(s)

(GD + GD ) × N

M

L

M

375 × (T + T )

P

L

t =

o

2

2

J : Rotor moment of inertia (kg¡m

2

)

M

GD : Motor GD (kg¡m

2

)

M

2

2

J : Load moment of inertia (kg¡m

2

)

L

GD : Load GD (kg¡m

2

)

L

2

2

N : Motor speed (min

−1

)

M

N : Motor speed (min

−1

)

M

T : Motor deceleration torque (N¡m)

P

T : Motor deceleration torque (kg¡m)

P

T : Load torque (N¡m)

L

T : Load torque (kg¡m)

L

NOTE

The built-in brake in servomotor with brake is a de-energization operation type, which is
used for holding purposes only and cannot be used for braking purposes. Use the holding
brake only to retain a stopped motor. Brake torque is more than about 120% of the rated
motor torque.

3