APPLICATIONS OF Σ-SERIES PRODUCTS

3.6.6 Using Mode Switch cont.

122

J

Selecting a Mode Switch

SERVOPACKs can use four types of mode switches. To select a mode switch, use the
following memory switch.

Memory

Switch Cn-01

Mode Switch Setting

Parameter

Unit

Bit

D

Bit

C

Bit

B

Mode Switch Setting

Parameter

Unit

1

Does not use mode

switch.

0

0

0

Uses torque reference as

a detection point.

(Standard setting)

Cn-0C

Percentage of rated

torque: %

0

1

0

Uses speed reference as

a detection point.

Cn-0D

Motor speed: min

−1

1

0

0

Uses acceleration refer-

ence as a detection point. Cn-0E

Motor acceleration:

10 (min

−1

)/s

1

1

0

Uses error pulse as a

detection point.

Cn-0F

Reference unit

When Torque Reference Is Used as a Detection Point of Mode Switch
(Standard Setting)

If a torque reference exceeds the torque value set
in parameter Cn-0C, the speed loop switches to P
control.

The SGDB SERVOPACK is factory set to this
standard mode (Cn-0C = 200).

Example of Use:

If a mode switch is not used and PI control is always performed, torque may enter a
saturation state during acceleration or deceleration, causing the motor speed to have
overshoot or undershoot.
Using the mode switch suppresses torque saturation and prevents the motor speed
from having overshoot and undershoot.

Without mode switch

Overshoot

Motor

speed

Undershoot

Time

With mode switch

Motor

speed

Time

3

Speed

Reference

speed

Motor

speed

Internal torque

reference

Torque

PI control

P control

PI control

PI control

P control