3.8 Special Wiring

145

The following is an example of wiring for noise control.

Noise filter

*

Servomotor

SGDB

SERVOPACK

(Casing)

• Operation relay se-

quence

• Signal generation cir-

cuit (provided by cus-
tomer)

3.5 mm

2

or more

Wire with a thickness of

3.5 mm

2

or more

Ground plate

Ground: One-line grounding

(at least class 3 grounding)

(Casing)

(Casing)

(Casing)

(Casing)

3.5 mm

2

or more

3.5 mm

2

or more

2 mm

2

or more

ground

200VAC

3.5 mm

2

or more

(Note b)

FG

* When using a noise filter, always observe the following wiring instructions:

Note

a) For a ground wire to be connected to the casing, use a thick wire with a thick-

ness of at least 3.5 mm

2

(preferably, plain stitch cooper wire).

b) For wires indicated by P↕, use twisted-pair cables whenever possible.

J

Correct Grounding

• Always ground the motor frame.

Always connect servomotor frame terminal FG to the SERVOPACK ground terminal

.

Be sure to ground the ground terminal

.

• If the servomotor is grounded via the machine, a switching noise current will flow from

the SERVOPACK power unit through motor stray capacitance. The above grounding is
required to prevent the adverse effects of switching noise.

• If the reference input line receives noise, do the following.

Ground the 0 V line (SG) of the reference input line. If the main circuit wiring for the motor
is accommodated in a metal conduit, ground the conduit and its junction box. For all
grounding, always use one-line grounding.