3.7 Forming a Protective Sequence

131

NOTE

Do not use the /S-ON signal to start or stop the motor. Always use an input reference to
start and stop the motor.

If the /S-ON signal is not to be used, set the following memory switch to 1:

Cn-01 Bit 0

Use of Servo ON Input Signal Factory

Setting: 0

For Speed/Torque Control

and Position Control

This memory switch is used to enable or disable
the servo ON input signal /S-ON (1CN-40).

When external short-circuit wiring is omitted, set
the memory switch to “1.”

Setting

Meaning

0

Uses servo ON signal /S-ON.

(When 1CN-40 is open, servo is OFF. When 1CN-40 is at 0 V, servo is ON.)

1

Does not use servo ON signal /S-ON.

(Servo is always ON. Equivalent to short-circuiting 1CN-40 to 0 V.)

3.7.3 Using Positioning Complete Signal

This section describes how to wire and use contact output-signal “positioning complete
output (/COIN).” This signal is output to indicate that servomotor operation is complete.

SGDB SERVOPACK

I/O power supply

Photocoupler output

Per output:

Maximum operation voltage:

30 VDC

Maximum output current:

50 mADC

/COIN+

/COIN−

3

SGDB SERVOPACK

When /S-ON is not used, this short-circuit

wiring can be omitted.

-40

(/S-ON)