Output → /clt 1cn-*1 – Yaskawa SGDB User Manual

Page 72

Advertising
background image

APPLICATIONS OF Σ-SERIES PRODUCTS

3.1.3 Restricting Torque

60

• Using /CLT Signal

This section describes how to use contact output signal /CLT as a torque limit output sig-
nal.

SGDB SERVOPACK

I/O power

supply

Photocoupler Output

Per output:

Maximum operation

voltage: 30 VDC
Maximum output

current: 50 mA DC

/CLT−

/CLT+

Output /CLT 1CN-*1

Torque Limit Output

For Speed/Torque

Control and

Position Control

This signal indicates whether motor output torque (current) is being restricted.

ON status: The circuit between 1CN-*1

and 1CN-*2

is closed.

1CN-*1

is at low level.

Motor output torque is being restricted.

(Internal torque reference is greater than the

preset value.)

OFF status: The circuit between 1CN-*1

and 1CN-*2

is open.

1CN-*1

is at high level.

Motor output torque is not being restricted.

(Internal torque reference is equal to or below

the preset value.)

Preset Value: Cn-08 (TLMTF)

Cn-09 (TLMTR)
Cn-18 (CLMIF) : P-CL input only
Cn-19 (CLMIR) : N-CL input only

Cn-2D

Output Signal Selection

Factory

Setting: 210

For Speed/Torque Control

and Position Control

Specifies the terminal to which /CLT is to be output.

Setting

Output terminals (1CN-)

g

*1

*2

1s place = 3

25

26

10s place = 3

27

28

100s place = 3

29

30

3

100s place = 3

10s place = 3

1s place = 3

(1CN-25, 26)
(1CN-27, 28)

(1CN-29, 30)

Torque

detection

/CLT