3.8.7 Using SGDB SERVOPACK with High Voltage Line

164

Connect cables of the same color to each other as shown in the table below. Note that
wiring for incremental and absolute encoders is different.

Signal

Name

Color and Wire Size of

Cable with Connectors

Color and Wire Size of

50-meter Extension

Cable (DP8409179)

PG5V

Red

AWG22

Red

AWG16

PG0V

Black

AWG22

Black

AWG16

PA

Blue

AWG26

Blue

AWG26

*

PA

White/Blue

AWG26

White/Blue

AWG26

PB

Yellow

AWG26

Yellow

AWG26

*

PB

White/Yellow

AWG26

White/Yellow

AWG26

PC

Green

AWG26

Green

AWG26

*

PC

White/Green

AWG26

White/Green

AWG26

PS

Purple

AWG26

Purple

AWG26

*

PS

White/Green

AWG26

White/Green

AWG26

RESET

White/Gray

AWG26

White/Gray

AWG26

BAT

Orange

AWG26

Orange

AWG26

BAT0

White/Orange

AWG26

White/Orange

AWG26

Note

Make sure to connect the shielded wires.

3.8.7 Using SGDB SERVOPACK with High Voltage Line

SGDB SERVOPACKs use three-phase 200 VAC.

If, however, three-phase 400 VAC class (400 V, 440 V) power supply must be used, pre-
pare the following power transformer (for three-phase).

<Primary side>

<Secondary side>

400 or 440 VAC

200 VAC

3

Only the absolute

encoder can be

connected.