APPLICATIONS OF Σ-SERIES PRODUCTS

3.8.2 Wiring for Noise Control

144

MCCB or Fuse for Each Power Capacity

SERVOPACK

Type

Power Capacity Per

SERVOPACK (kVA)

(see note 1)

Current Capacity Per MCCB or

Fuse (A)

(see note 2)

SGDB-03ADj

0.65

5

SGDB-05ADj

1.1

5

SGDB-07ADj

1.5

8

SGDB-10ADj

2.0

8

SGDB-15ADj

2.5

10

SGDB-20ADj

4.0

12

SGDB-30ADj

5.0

18

SGDB-44ADj

7.0

24

SGDB-50ADj

7.5

28

SGDB-60ADj

12.5

32

SGDB-75ADj

15.0

41

SGDB-1AADj

19.0

60

SGDB-1EADj

30.0

80

Note

1) Power capacity at rated load

2) Operating characteristics (25°C): 2 seconds or more for 200%, 0.01 second or more for

700%

3) A fast-operating fuse cannot be used because the SERVOPACK power supply is a ca-

pacitor input type. A fast-operating fuse may blow out when the power is turned ON.

3.8.2 Wiring for Noise Control

J

Example of Wiring for Noise Control

This SERVOPACK uses high-speed switching elements in the main circuit. It may re-
ceive “switching noise” from these high-speed switching elements if wiring or grounding
around the SERVOPACK is not appropriate. To prevent this, always wire and ground the
SERVOPACK correctly.

This SERVOPACK has a built-in microprocessor (CPU). To protect the microprocessor
from external noise, install a noise filter in place.