Yaskawa SGDB User Manual
Page 229
USING THE DIGITAL OPERATOR
4.2.9 Current Detection Offset Manual Adjustment Mode cont.
218
7. Press the
and
keys to adjust the
amount of current detection offset.
8. Press
DSPL
SET
to return to the parameter data
display.
9. Press
DATA
ENTER
to return to the parameter setting
mode display. This ends the current detection
offset manual adjustment.
For JUSP-OP03A
1. Press
MODE/SET
to select the parameter setting
mode.
2. Press the
UP
and
DOWN
to select the parameter
number Cn-00.
Parameter Cn-00 is selected when the power is
turned ON.
3. Press
DATA
to display the current data for the pa-
rameter Cn-00.
4. Press the
UP
and
DOWN
keys to change the data
to 08.
5. Press
MODE/SET
to select the current detection off-
set manual adjustment mode.
The amount of current detection offset is dis-
played.
6. Press
DATA
to switch between U-phase and V-
phase current adjustment modes.
7. Press the
UP
and
DOWN
keys to adjust the
amount of current detection offset.
4
Setting Mode Display
JUSP-OP03A
Setting Mode
Select Cn-00.
Parameter Number
Data
Set to 00-08.
Press
the keys
to
change
the value
Current Detection
Offset Manual
Adjustment Mode
Phase-u
Current
Adjustment
Mode
Phase-v
Current
Adjustment
Mode