3.7 Forming a Protective Sequence
135
Example: Outputting a /V-CMP signal
Cn-2D=jj0
(/V-CMP is output to 1CN-25 and 1CN-26 only.)
Preset
Value
Function
0
/COIN, /V-CMP
(Can be allocated to 1CN-25 and 1CN-26 only.)
1
/TGON
2
/S-RDY
3
/CLT
4
/BK
5
Overload warning
6
Overload alarm
Set the following parameter to specify the output conditions for speed coincidence signal
/V-CMP.
Cn-22
VCMPLV Speed Coincidence
Signal Output Width
Unit:
min
−1
Setting
Range: 0
to 100
Factory
Setting:
10
For Speed
Control Only
Set the output conditions for speed coincidence
signal /V-CMP (1CN-25).
/V-CMP signal is output when the difference be-
tween the reference speed and actual motor
speed is not greater than the preset value.
Example: When preset value is 100 and reference speed is 2000 min
−1
.
/V-CMP is ON (circuit between 1CN-25 and 1CN-26 is closed) when the speed
is between 1900 and 2100 min
−1
.
NOTE
/V-CMP is a signal for speed control.
For position control, /COIN (position complete output) is used instead. For torque control,
/V-CMP is always ON.
3
Motor
speed
Reference
speed
V-CMP is output
within this range