3.7 Forming a Protective Sequence

135

Example: Outputting a /V-CMP signal

Cn-2D=jj0
(/V-CMP is output to 1CN-25 and 1CN-26 only.)

Preset

Value

Function

0

/COIN, /V-CMP
(Can be allocated to 1CN-25 and 1CN-26 only.)

1

/TGON

2

/S-RDY

3

/CLT

4

/BK

5

Overload warning

6

Overload alarm

Set the following parameter to specify the output conditions for speed coincidence signal
/V-CMP.

Cn-22

VCMPLV Speed Coincidence

Signal Output Width

Unit:

min

−1

Setting

Range: 0

to 100

Factory

Setting:

10

For Speed

Control Only

Set the output conditions for speed coincidence
signal /V-CMP (1CN-25).

/V-CMP signal is output when the difference be-
tween the reference speed and actual motor
speed is not greater than the preset value.

Example: When preset value is 100 and reference speed is 2000 min

−1

.

/V-CMP is ON (circuit between 1CN-25 and 1CN-26 is closed) when the speed
is between 1900 and 2100 min

−1

.

NOTE

/V-CMP is a signal for speed control.
For position control, /COIN (position complete output) is used instead. For torque control,
/V-CMP is always ON.

3

Motor

speed

Reference

speed

V-CMP is output

within this range