3.6 Minimizing Positioning Time

123

When Speed Reference Is Used as a Detection Point of Mode Switch

If a speed reference exceeds the value set in pa-
rameter Cn-0D, the speed loop switches to P con-
trol.

Example of Use:

The mode switch is used to reduce settling time.
Generally, speed loop gain must be increased to reduce settling time. Using the
mode switch suppresses the occurrence of overshoot and undershoot when
speed loop gain is increased.

Without mode switch

Speed reference

Motor

speed

Motor speed

Settling time is long

Increase speed loop gain

Without mode switch

Motor

speed

Overshoot

Undershoot

Time

With mode switch

Motor

speed

Settling time

Suppress the occurrence

of overshoot and

undershoot.

When Acceleration Is Used as a Detection Point of Mode Switch

If motor acceleration exceeds the value set in pa-
rameter Cn-0E, the speed loop switches to P con-
trol.

Example of Use:

If a mode switch is not used and PI control is always performed, torque may enter a
saturation state during acceleration or deceleration, causing the motor speed to have
overshoot or undershoot.
Using the mode switch suppresses torque saturation and prevents the motor speed
from having overshoot and undershoot.

Without mode switch

Motor

speed

Overshoot

Undershoot

Time

With mode switch

Motor

speed

Time

3

Speed

Speed reference

Motor

speed

PI control

P control

PI control

Speed

Reference

speed

Motor speed

Motor

acceleration

Acceleration

PI control

P control

P control

PI control

PI control