Reclosing (optional), Inputs and outputs, Reclosing (optional) -48 – Basler Electric BE1-700 User Manual

Page 104: Inputs and outputs -48, Reclose initiate (ri) -48, Breaker status (status) -48, Figure 4-46. reclosing logic block -48, Figure 4-47. recognition dropout timing -48

Advertising
background image

RECLOSING (OPTIONAL)

The BE1-700 reclosing function provides up to four reclosing attempts that can be initiated by a protective
trip or by one of the contact sensing inputs. The reclosers allow supervisory control and coordination of
tripping and reclosing with other system devices. Any of the four recloser shots can be used to select a
different setting group when the appropriate shot is reached in a reclosing sequence. This change in
setting groups allows changing protection coordination during the reclosing sequence. For example, you
could have a fast 51 curve on the first two trips in the reclosing sequence and then switch to a new group
on the second reclose that uses a slow 51 curve. Detailed information about relay setting groups can be
found earlier in this section under the heading of Setting Groups. Recloser function block inputs and
outputs are shown in Figure 4-46 and are described in the following paragraphs. An overall logic diagram
for the recloser function is shown in Figure 4-54.

Figure 4-46. Reclosing Logic Block

Inputs and Outputs

Reclose Initiate (RI)

The RI input is used with the 52 status input to start the reclose timers at each step of the reclosing
sequence. To start the automatic reclose timers, the RI input must be TRUE when the breaker status
input indicates that the breaker has tripped. To ensure that the RI input is recognized, a recognition
dropout timer holds the RI input TRUE for approximately 225 milliseconds after it goes to a FALSE state.
This situation might occur if the RI is driven by the trip output of a protective function. As soon as the
breaker opens, the protective function will drop out. The recognition dropout timer ensures that the RI
signal will be recognized as TRUE even if the breaker status input is slow in indicating breaker opening.
Figure 4-47 illustrates the recognition dropout logic and timing relationship.

Figure 4-47. Recognition Dropout Timing

Breaker Status (STATUS)

This input is used to indicate to the recloser function block that the breaker is closed. A TRUE signal at
this input indicates a closed breaker.

4-48

BE1-700 Protection and Control

9376700990 Rev M